Troubleshooting the Drive
6-11
6.4.3 Accessing, Reading, and Clearing the Faults in the Error Log
The following procedure shows how to access and clear the error log. Note that you 
cannot clear a single entry from the error log. The entire log, including all the fault 
codes and the day and time stamp of each fault, will be cleared simultaneously using 
this procedure.
SrL
Communication 
loss between 
Regulator/PC/OIM
Serial port communication cable, PC 
or OIM communication port setup.
Check connection cable and 
communication port setup.
UAr
Spurious host PC 
comm interrupt
Regulator board failure.
Replace Regulator board.
UbS
Asymmetrical bus 
fault. Look at the 3 
LEDs on the Power 
Module Interface 
board. They 
indicate which fault 
has occurred by 
flashing in unison.
1 = Input Ground 
Fault;
2 = Asymmetrical 
Bus;
3 = Slow Ramp 
Rate of DC Bus
One of 3 differnet faults has occurred;
1. Input Ground Fault - Excessive 
current flowing bwtween any of the 
three input phases and earth ground.
2 . Asymmetrical Bus - When 
measuring between the cap bank 
midpoint and the +DC bus and -DC 
bus, there is a 200 V or greater 
mismatch.
3. Slow Ramp Rate of DC Bus - DC 
bus did not change to the ful value 
given time allowed. Can occur only at 
power-up. 
1. Check the connection from the 
current transformer to the Bus Control 
board.
2. Replace shorted capacitor, fix loose 
connection, or replace discharge 
resistor.
3. Turn on drive. If UbS is displayed, 
turn drive off and then on again very 
quickly. If the UbS fault goes away and 
the DC bus charges, replace the Bus 
Control board.
Table 6.3 – List of Fault Codes (Continued)
Code
Fault
Description
Fault Cause
Corrective Action
Step 1. Press the PROGRAM key. 
The First Menu General parameters are 
displayed. The PROGRAM LED will turn on.