The following table summarizes the peak (at startup) power consumed by the system and the heat it generates
under the maximum processing load produced by a Visual Effects, Finishing, or Colour Grading application.
For more detailed specifications, including noise output, see the documentation provided by the manufacturer.
Heat (BTUs)
Watts
Cont. Amps (120V
/ 240V)
Startup Amps
(120V / 240V)
Quantity
Component
1556
456
3.8 / 1.9
4.0 / 2.0
1
Workstation (with cards)
205
60
0.5 / 0.25
0.5 / 0.25
1
Lucid ADA 88192
1140
334
2.78 / 1.39
3.8 / 1.9
1
Stone
®
 Direct XR storage
chassis
942
276
2.3 / 1.15
3.75 / 1.88
1
Stone Direct XE expansion
chassis
2130
624
5.2 / 2.6
6.41 / 3.2
1
Stone Direct XR + Stone
Direct XE
410
120
1 / 0.5
1 / 0.5
1
Autodesk
®
 Control Surface
(Lustre only)
You must be able to meet the startup power requirement and have a climate control system with the capacity
to maintain the temperature of these components under the maximum processing load. The following table
shows standard conversion benchmarks and an example of how they can be used to determine climate
control requirements.
Example
Unit Conversion
456 Watts = 1556.33 BTU
1 Watt = 3.413 BTU
1556.33 BTU = 0.13 Tons of air conditioning
12000 BTU = 1 Ton of air conditioning
Rack Mount Requirements
If you plan to rack-mount your system, allow sufficient space for each component, as indicated in the
following table.
Required Rack Space
Form Factor
Quantity
Component
5U
5U
1
Workstation
1U
1U
1
AJA OEM-2K breakout box
2U
2U
1
Stone Direct XR storage chassis
2U
2U
1
Stone Direct XE expansion chassis (optional)
Avoiding Damage from Static Electricity
Take precautions to prevent damage to sensitive components from static discharge:
Make sure power is turned off on the component you are working on. It is a good idea to unplug
components until all other connections are configured.
10 | Chapter 2   Getting Started