Aquacal HP7 Manuale Utente

Pagina di 29
WARNING !!!!  Dealer &  Service Center Use Only 
8)  [DEL] will display (At this point you have entered the service menu, and service-
level programming will be possible.); 
9)  Push Pool/Spa pad until [LOC] appears on readout for the second time; 
10) Push the up arrow,…The current, correct lock code will display.  Using the up or 
down arrow, the code can now be changed back to back to the factory default: 
“50”, or the code may be set to any number ranging [000] to [999].  Unless 
attempting to prevent tampering,  the factory code setting “50”  is recommended: 
 
 
LEVEL-2 DISPLAY  SET UP & CALIBRATION CODES 
 
Listed are all service adjustable parameters, paired with the factory default settings and range of 
adjustment. 
       
 
Display 
Code 
Description Factory 
Setting 
Range 
 
[LOC] 
Service Lock Code Entry  
050 
0 - 999 
[dEL] 
Anti-Short Cycle 4 min. Time 
Delay 
0 / 1 
[JAO] 
Jandy / Compool Controller 
Interface 
0 / 2 / 3 
[FS2] Flow 
Switch/Automatic 
Thermostat Switching 
0 / 1 
[tSC] 
Water Sensor Calibration 
Factory 
Calibrated 
+ 10
° to -10° of 
displayed value
[dSC] 
Defrost Sensor Calibration 
Factory 
Calibrated 
+ 10
° to -10° of 
displayed value
[db1] 
Thermostat Dead Band Differential
0.8
°  
0.2
° to 2.0° of 
displayed value
 
 
TROUBLESHOOTING 
 
The heat pump microprocessor control in is designed to be self-diagnostic through the use of 
various fault codes displayed in the event of a problem. If you believe you are experiencing a 
problem with the heater, and need to call for service, it will be beneficial to let the telephone 
representative know which code is displayed. This information will allow the service 
personal to better understand the problem when responding to the call. Listed on the 
following page is list of all fault messages- and what they mean- along with possible causes 
and solutions for the error. 
 
16