Bosch Appliances Smoke Alarm FPD-7024 Manuale Utente
4 Zone input terminal strip
10 NAC terminal strip
5 Option bus terminal strip
11 Auxiliary power terminal strip
6 FPC-7034 point expander connector
pins
Components
On-board conventional points
All on-board points and points implemented with the FPC-7034 work with two- or four-wire
detectors. The system has an optional alarm verification feature.
detectors. The system has an optional alarm verification feature.
Number of two-wire circuits
Four circuits, expandable to eight using an
FPC-7034 Expander
FPC-7034 Expander
Type of Circuit
Class B, Style B and Class A, Style D as
needed)
needed)
EOL Resistor
2.21 kΩ (P/N: 25899 or F01U034504), UL
listed
listed
Supervisory Existing
8 mA to 20 mA
Required Existing for Alarm
25 mA
Maximum Short Circuit Existing
45 mA
Maximum Line Resistance
150 Ω
Circuit Voltage Range
20.4 VDC to 28.2 VDC
Maximum Detectors per Point
20 detectors (two-wire)
Total Detector Standby Existing
3 mA maximum
Response Time
1
Either fast (500 ms) or programmable (from
1 second to 89 seconds)
1 second to 89 seconds)
Dirty Detector Monitoring
Implements Bosch Security Systems, Inc.
Chamber Check and GE Interlogix, Inc.
CleanMe protocol to monitor conventional
loops for dirty detectors.
Chamber Check and GE Interlogix, Inc.
CleanMe protocol to monitor conventional
loops for dirty detectors.
1
Table 2.1: Two-wire circuits
All on-board points, and points activated with the FPC‑7034 Four Point Expander, are
continuously monitored for detectors signaling a dirty condition using the Bosch Security
Systems, Inc. Chamber Check and GE Interlogix, Inc. CleanMe protocols. To prevent nuisance
reports, a two-minute delay occurs before a dirty detector is annunciated. A six-minute delay
occurs after the detector restores from the dirty condition before the control panel restores
the condition.
continuously monitored for detectors signaling a dirty condition using the Bosch Security
Systems, Inc. Chamber Check and GE Interlogix, Inc. CleanMe protocols. To prevent nuisance
reports, a two-minute delay occurs before a dirty detector is annunciated. A six-minute delay
occurs after the detector restores from the dirty condition before the control panel restores
the condition.
Off-board addressable points (with D7039 Multiplex Expansion Module)
The D7039 Multiplex Expansion Module adds:
–
–
Two Class B, Style 4 or one Class A, Style 6 Signaling Line Circuits (SLCs)
2.2
2.2.1
2.2.2
Fire Alarm Control Panels
Overview | en
9
Bosch Security System, Inc.
Installation and Operation Manual
2012.08 | 04 | F01U008458