7.0 Telephone 
Connections 
7.1 Registration 
The Bosch Security Systems D9412GV2/D7412GV2 
Control Panels are registered with the Federal 
Communication Commission (FCC) under Part 68, for 
connection to the public telephone system using an 
RJ31X or RJ38X jack installed by the local telephone 
company. 
 
 
An RJ31X jack can be modified by placing a 
jumper wire between Terminals 2 and 7 to 
become an RJ38X jack. 
7.2 Notification 
Do not connect registered equipment to party lines or 
coin-operated telephones. Notify the local telephone 
company and provide the following information before 
connecting the control panel to the telephone network: 
 
The particular line to which the control panel will 
be connected 
 
Make (Bosch Security Systems), model 
(D9412GV2 or D7412GV2), and serial number of 
the control panel 
 
FCC registration number: AJ9MUL-46532-AL-E 
 
Ringer equivalence for the control panel: 0.4B  
7.3 Location 
To prevent jamming of signals, wire the RJ31X or 
RJ38X jack before the in-house telephone system to 
support line seizure (Figure 7). Install the jack on the 
street side of the telephone switch, wired ahead of any 
PBX equipment. Line seizure temporarily interrupts 
normal telephone usage while the control panel sends 
data. After installation, confirm that the control panel 
seizes the line, acquires dial tone, reports correctly to 
the receiver, and releases the telephone line to the in-
house telephone system. 
 
Figure 7: 
RJ31X Wiring 
4
5
8
4
5
8
4
5
8
1
1
1
T1
T
R
R1
RING (red)
TIP (green)
RJ31X
2
7
1
2
3
4
5
6
 
1 -  RJ31X Jack 
2 -  (TIP) 
3 -  (RING) 
4 -  Telco connector block 
5 -  Outside telco 
6 -  Premises telephone 
 
7.4 
Telephone Cord Connection 
Connect one end of a D161 (2.1 m [7 ft.]) or a D162  
[61 cm (2 ft.)] Telephone Cord to the telco cord 
connector located on the bottom left corner of the 
control panel. Refer to Figure 8. Connect the other end 
to the RJ31X or RJ38X jack. 
 
 
To supervise the phone cord, use an RJ38X 
jack. 
 
Figure 8: 
Phone Connector, Phone LED, and Operation Monitor LED Locations 
12
11
13
15
14
16
18
17
19
21
20
22
PHONE
LED
RED
ON when
communicating
OFF when idle
PHONE LINE SEIZED
TIP
RING
TELCO
RING
TIP
PHONE LINE
   SEIZED
1
2
3
GRN
Point 8
S3 Option
Closed = 1K
Ω
 EOL
Normal Operation
Open =AB-12 UL
Bell Box 220 K
Ω
D5200/D5360
PROG CONN
TELCO CORD
MODEL D161
 
1 -  Phone LED (red) 
2 -  Telephone cord connector 
3 -  Operation Monitor LED (green)