BLACKHAWK! Power Supply Blackhawk Series Broadband Power Supplies Manuale Utente

Pagina di 31
Emergency Shutdown Procedure 
 
 
DANGER 
 
Exercise extreme caution when performing the following procedure.  Carry 
out the steps precisely in the order given to avoid the possibility of personal 
injury or equipment damage. 
 
Perform the following procedure if the power supply must be shut down and disconnected 
on an emergency basis: 
 
1.  Switch the BATTERY CIRCUIT breaker to the OFF position. 
 
2.  Disconnect the AC power cord from the outlet in the cabinet. 
 
3.  Remove the BATTERY connector from its location at the power supply front panel. 
 
4.  Disconnect the output cable from the OUTPUT connector at the power supply front 
panel. 
 
5.  Within the service entrance box or branch circuit box, operate the AC input circuit 
breaker for the power supply to the OFF position. 
 
General Safety Issues
 
The power supply documented in these instructions has been designed, tested and 
produced to ensure safe, trouble-free operation.  Personnel using or installing this power 
supply should completely read and fully understand the following safety instructions.  They 
are provided here as informational guidelines for your continued safety in usage of the 
product.  These general safety issues should be observed in all phases of power supply 
installation and service. 
 
This power supply uses two sources of electrical power: commercial AC and DC derived 
from a battery.  Whenever performing maintenance on any of the internal components, you 
must disconnect both the battery cable and AC line cord. 
 
Always use proper lifting techniques when handling the power supply or batteries.  Both the 
power supply and a single 12-volt battery weigh approximately the same, about 65 pounds 
(30 Kg). 
 
Personnel installing or servicing batteries must wear eye protection (goggles or full face 
shield) and protective clothing (apron and gloves) as mandated by standard operating 
procedures.  Additionally, only fully insulated tools specifically designed for battery 
installation and service should be used for that purpose.  Tools wrapped with vinyl or fabric-
based electrical tape are NOT acceptable substitutes. 
 
6