Installation
3-3
B1272M001
     
BARNETT ENGINEERING LTD.
ProTalk Cv2
Figure 6   +12 Volt Input Wiring
Figure 7    +5 VDC Input Wiring
Figure 9  
 
Analog (unfiltered) Input Wiring
Figure 8   Analog (filtered) Input Wiring
3.3.2  +12 volt alarm signal
The input will accept an alarm signal
that switches between 0 and +12 volts
with the wiring arrangement shown in
Figure 6.  
If the signal switches between +12 volts
and an open circuit, as in the case of a
relay contact, the ‘B’ terminal must be
connected to ground to ensure that the
logic level goes to ground when the
voltage is removed. 
3.3.3  +5 volt alarm signal
Figure 7 shows how an alarm signal that
switches between +5 volts and ground is
wired.  If the alarm signal does not have a
true ground level, terminal ‘B’ must be
connected to ground.
 
3.3.4  Analog input (Advanced mode)
For analog signals, either of the wiring configurations shown in Figures 8 and 9 can be used. 
The connection shown in Figure 8 will provide additional filtering of the signal.