Specifications
8-1
B1272M001
     
BARNETT ENGINEERING LTD.
ProTalk Cv2
8  Specifications
8.1  General
Alarm Inputs
• 8 inputs: analog or digital, latching or momentary; plug in
screw terminal block.
• analog: 0 to 5 VDC, 100k input impedance
• digital: normally open or normally closed, ground closure
or +10 to +30 VDC input; optionally configured for
acknowledge input.
Control Outputs
• 8 independent open collector outputs controlled by DTMF
codes; voice announcement when operated; plug in screw
terminal block; optionally configured for alarm status
indication.  Rated 0.4 A, 50 volts max.
Programming Connection
• DB9 - RS232, 9600 baud
Record Connection
• RJ11, using standard telephone set
Voice Quality
• Digitized, toll quality, 32 kbps ADPCM
Power
• +11 to +28 VDC, 125 mA idle, 750mA transmitting; plug
in screw terminal block
Environment
• -30
o
C to +50
o
C
Physical
• 8.5"L x 6.0"W x 3.0"D
Cellular Telephone
• Internal Kyocera M200 CDMA
Antenna Impedance
• 50 ohms
8.2  Programmable Features
Voice Messages
• Site identification, Group identification, Alarm inputs, and
control outputs;  60 seconds maximum, non-volatile
Alarm Type
• Individually configured for digital normally open, digital
normally closed, or analog 0-5 V
Analog Alarm Range
• -999.9 to +999.9 
Alarm Groups
• Alarms can be assigned to one of 8 groups.  All alarms in a
group use the same directory when calling out.
Shifts
• Up to 4 shifts can be used.  The current setting of the shift
instructs a group to use one of the six directories.
Interval Timer
• Two-stage timer which uses the short interval several times
before switching to a long interval.  Short and long