29 
 
4.4 
Ventilation 
UPS can  work  in a continuous environment  within 18°F[-10°C] to 104°F [+40°C ]  temperature  range,  although,  
ideally  the ambient temperature should be below  78°F [25°C]. 
The heat, dissipated  by the UPS (indicated on  figure  7),  is extracted by internal fans and then dissipated into the air. 
The  heat  can be removed from the UPS room by a  forced  cooling ventilation system or, alternatively, an air 
conditioning system. 
The required air changes per hour will depend on the UPS rating and this heat loss and on the cooling air temperature. 
To calculate the required air flow for the dissipated power, the altitude and the cooling air temperature, the following 
equation can be used: 
• 
P
V  = 2770   - - - - - - • e 
(0.125 h T
k
 / T
0
 )
  
 
T
r
 - T
with:  
=  
air flow [mc/h] 
P
d
 
=   total dissipated power [kW] 
T
r
 
=   max.  temperature allowed into the room [104°F = 40°C = 313°K] 
T
k
 
=   Temperature of input cooling air 
T
0
 
=   273 °K 
h  
=   altitude above the sea level [km]