8.2 TROUBLESHOOTING GUIDE
TROUBLE/ INDICATION 
POSSIBLE CAUSE 
SUGGESTED REMEDY
No AC output –
DC input below
Recharge or replace
red LED lit
10 volts
battery
No AC output – 
Excessive appliance
Reduce load-wait for 
red LED lit 
load-thermal shutdown 
inverter to cool. Turn off
Low battery alarm 
Bad connection 
Tighten all DC 
sounds continuously  
or wiring
connections
Low battery  
Low battery voltage 
Recharge battery
alarm sounds
Remove load from 
inverter while recharging
battery
Motorized power tool 
Excessive start-up load
Rock the on/off switch 
won’t start  
several times. If appliance 
does not start, then
appliance will not work
with inverter
Motorized power tool 
Purely inductive load
Make the load not purely
does not operate at 
inductive. Operate an 
correct speed
incandescent lamp at
same time as motor
Television/radio 
Snow in picture, buzz 
Keep inverter and
interference
in speaker  
antenna distant from 
each other. Use shielded
antenna cable. Connect
antenna to amplifier and 
ground inverter case
9.0   MAINTENANCE
Inverters require minimal maintenance. However, for optimum performance, per-
form the following:
1. Turn off the inverter using the front panel on/off switch.
2. Disconnect the inverter by removing the DC power fuse.
3. Check and tighten all electrical connections, including the ground.
4. Using a non-metallic vacuum cleaner hose, vacuum the fan area and 
other air slots.
5. Clean any dirt and dust from the outside of the unit with a damp cloth.
6. Reconnect the fuse and resume operation