Data Logging Setup
9300 Series User’s Guide
Page 46
Chapter 3 - Default Meter Functionality
Procedures for changing the logging depth and the frequency of logging are
discussed in the following sections: “Changing the Frequency of Logging” on
page 47 and “Changing the Log Depths” on page 47.
discussed in the following sections: “Changing the Frequency of Logging” on
page 47 and “Changing the Log Depths” on page 47.
Default Logging Configuration
The standard configuration of the meter includes data recorders that log various
power system data such as energy and demand, or the average power system
quantity used over a period of time (Historic Mean Log). The 9350 also logs sags
and swells in voltage.
power system data such as energy and demand, or the average power system
quantity used over a period of time (Historic Mean Log). The 9350 also logs sags
and swells in voltage.
Revenue Logging
For the revenue meter option, Data Recorder #1 is locked, so channels must be
specified prior to the meter being sealed. Refer to RMICAN Ordering Sheet on our
website for your particular meter.
specified prior to the meter being sealed. Refer to RMICAN Ordering Sheet on our
website for your particular meter.
For compatibility with the UTS MV-90 billing software, Data Recorder #1 must be
configured as a 16-channel recorder.
configured as a 16-channel recorder.
Historical Data Logging
One Data Recorder module, the Historic Mean Log, logs the following output
register values by default:
register values by default:
WinPM.Net Reporting
One recorder is configured to provide power system data for the Reporter
software. This recorder is labeled Egy Dmd Log. If any input links to this module
are changed, Reporter will not be able to create reports from the device’s logs. If
you use the Reporter software, do not change the parameters that are logged in the
Egy Dmd Log.
software. This recorder is labeled Egy Dmd Log. If any input links to this module
are changed, Reporter will not be able to create reports from the device’s logs. If
you use the Reporter software, do not change the parameters that are logged in the
Egy Dmd Log.
Hist Mean Log
Vll avg mean
Vln avg mean
I avg mean
kW tot mean
kVAR tot mean
kVA tot mean
PF sign mean
Freq mean
V unbal mean
I unbal mean
V1 THD mean
V2 THD mean
V3 THD mean
I1 THD mean
I2 THD mean
I3 THD mean