Analog I/O Modules (AD268 / DA264 / TC218)
7. Troubleshooting
PART 3 TC218
7.2 Troubleshooting
The table below shows the trouble and its remedy.
Trouble
Module
status info
LED
Module operation
Cause
Remedy
Input type
setting error
setting error
Bit 7 is ON
ON
(if the error
occurs in all
channels, it
is OFF)
(if the error
occurs in all
channels, it
is OFF)
The error channel
stops the
conversion. The A/D
conversion data is 0.
stops the
conversion. The A/D
conversion data is 0.
Invalid input type
parameter was set.
parameter was set.
Set the correct
input type
parameter.
input type
parameter.
Thermocouple
burnout
burnout
Bit 8 is ON
ON
The A/D conversion
data of the channel
is 32767 (H7FFF).
data of the channel
is 32767 (H7FFF).
The thermocouple
input wire becomes
open.
input wire becomes
open.
Check the
thermocouple.
thermocouple.
Analog signal
limit over
limit over
Bit 9 is ON
ON
The A/D conversion
data of the channel
is limited by the limit
value.
data of the channel
is limited by the limit
value.
Analog input signal
is out of the range.
is out of the range.
Check the signal
source (sensor).
source (sensor).
MPU error
Bit A is ON
OFF
The A/D conversion
is stopped.
is stopped.
Internal processor
operation is not
normal.
operation is not
normal.
Execute reset
command, or
cycle power off
and on.
command, or
cycle power off
and on.
ROM error
Bit B is ON
OFF
The A/D conversion
is stopped.
is stopped.
EEPROM data
error is detected.
error is detected.
Cycle power off
and on.
and on.
DP-RAM error Bit C is ON
OFF
The A/D conversion
is stopped.
is stopped.
Buffer memory
access error is
occurred.
access error is
occurred.
Cycle power off
and on.
and on.
External 24V
error
error
Bit E is ON
OFF
The A/D conversion
is stopped.
is stopped.
Internal
±
15V
voltage is not
normal.
normal.
Check the
external 24Vdc
power supply.
external 24Vdc
power supply.