.  8 powered outputs
.  Controls solenoids and relays
.  Common load supply of up to 265 V ac
.  Discrete or pulsed outputs
.  1A per channel maximum
.  20–265 V ac bussed field power required
Module Specifications  
Outputs
Number of channels ...........................................................................8
Output voltage range.....................................................20–265 V ac
Frequency ............................................................................50 / 60 Hz
ON voltage drop........................................................................< 1.2 V
OFF leakage current .................................................................< 4mA
Switched current per channel ††
     Continuous.................................................................................1 A*
     For < 100 ms.................................................................................5 A
     For < 20 ms.................................................................................20 A
Minimum load current, per channel
     @ 115 V ac...............................................................................11 mA
     @ 230 V ac.................................................................................5 mA
Configurable Parameters
Output initialization state...................................predefined value
Fail-safe.................................................predefined value/last value
Output .....................discrete, momentary or continuous pulse‡
Pulse width.....................................................................2 ms to 130 s
Response Time
Response time (max.) ..2 ms + 1/2 cycle of mains frequency
(From Railbus command to output change)
Power Supplies
Railbus (12V) current......................................................75 mA (typ.)
..........................................................................................125mA (max.)
Bussed Field Power (voltage)....................................20 to 265 V ac
NT
-8116-DO-AC
Image Description
8-channel Discrete Output
20–265 V ac, non-isolated, module powered
Mechanical
Module Key Code .............................................................................F1
Module width ............................................................................42 mm
Weight............................................................................................220 g
Field Terminals 
Field Wiring
Recommended 
Field Terminal
Compatible 
Field Terminal
General Purpose
NT-8604-FT-FU
Fused
NT-8602-FT-ST
Standard †
Class 1, Div 2 
or Zone 2 hazard-
ous area
NT-8611-FT-FU
Non-arcing,
Fused
NT-8610-FT-NA
Non-arcing †
† Alternative fusing in the field wiring is recommended if it is 
not provided in the field terminal.
†† Stated figures are for operation with unfused field termi-
nal. When operating with 2 A fused field terminal part no. 
NT-8604-FT-FU, maximum switched current is 5 A inrush for 
<10 ms pulse width at 0.1% duty cycle and <108 operations
*Limited to 3 A per module.
‡Consult NovaTech for availability
NovaTech 8000 Series I/O Family
Copyright © 2007 NovaTech, LLC. All rights reserved. All trademarks 
are properties of their respective owners. NovaTech is a registered 
trademark  of  NovaTech,  LLC.  The  information  in  this  literature  is 
subject to change without notice and is not to be construed as a 