Varec TankGate Interface 8315 Series Manuale Utente

Pagina di 120
8315 L&J Tankway Interface Module
TankGate Interface
18 
Installation and Operations Manual
• 
COM: Communication between the TankGate and the host computer
• 
TXD: Transmitting data to tank gauge 
• 
RXD: Receiving data from tank gauge
• 
+5V: Indicates interface module power
• 
+VEXT: Indicates external power
Figure 3-5: Model 8315 LED Indicators
3.2.3
External Power Connector (+48V) (J2)
Connect the +48 VDC External Power as shown below:
Figure 3-6: External Power Connector
3.2.4
Surge/Shield Ground Connector (J4) 
Connecting the Surge/Shield ground connector
Caution!
This ground connection is important for system safety.
• 
Connect a 14 AWG copper wire between the ground terminal (J4) and a good 
earth ground. Perform this step before connecting ANY other wires.
• 
Verify that the resistance in this connection does not exceed 1 ohm.