Varec TankGate Interface 8315 Series Manuale Utente

Pagina di 120
8315 L&J Tankway Software Description
TankGate Interface
54 
Installation and Operations Manual
Maxtime
Specifies the maximum time (in secs) between automatic Change of 
State data being sent to the Host in response to a Change of State 
Request.  Report must be set to either Low or High for the Value 
parameter to be sent in response to a Change of State Request.  A value 
of 0 disables this option.  Non-zero values cause responses to be sent 
even if the value has not changed since the last message.  The 
maximum is 255 seconds.  The default is 240.
Watchdog
Enables the watchdog task on the Motherboard.  The watchdog task 
monitors the LJ1000 point on the Model 8315 and verifies it is scanning 
for gauges.  If the Model 8315 fails, the 0x4000 and the 0x0010 bits of 
the PntStatus will be set to indicate the failure.
Dynamic Parameters
Function
Level
Floating point value representing the tank level (in feet).
Temp
Floating point value representing the tank temperature (in 
Fahrenheit).
PntStatus
Integer HEX value indicating status of point.  Values are:
0x0001: Dual Band Error 
0x0002: Scan Timeout
0x0004: Internal Module Error
0x0008: Missing Comm Board
0x0010: Gauge Not Responding
0x0020: Blown Transmit Fuse
0x0040: Parity Error
0x0080: Tankway Error
0x4000: Failure of the Model 8215.  This bit is set if the Watchdog 
task on the Motherboard determines that the Model 8215 has 
stopped updating.
GaugeStatus
Byte value indicating status of the gauge. Values are:
0x01: Dual Band Error
0x02: Temperature value is positive
0x04: Transmitter Error
0x08: Missing Comm Board
AlarmTime
Time that alarm first occurred.  The point is in alarm when the 
PntStatus is non zero.
Elapse
Time of the last scan.
ScanTime
Time of the last good reading.  A reading is considered good if it 
has no parity or time-out error, and has passed the filter criteria.
Raw1
Raw data from gauge. Value reported as hexadecimal value.
Raw2
Raw data from gauge. Value reported as hexadecimal value.
PntCheckSum
CRC-16 Checksum for point's static Configuration Parameters.
Configuration 
Parameters
Function