REMINGTON QFP40 Direct Vent FIREPLACE
250-4721   JUNE 2001
ADJUSTMENTS
HIGH ALTITUDE OPERATION
In Canada, this unit is approved from 0 to 4500 feet above sea level. Installation of this
stove at altitudes above 4500 feet is subject to field test of the individual installation and approval
by the local authority having jurisdiction.
In the United States, input ratings of this unit are based on sea level operation, and shall
not be changed for operation at elevations up to 2000 feet. For operation at elevations above
2000 feet, this stove shall be reduced at the rate of 4% for each 1000 feet above sea level.
Exception:  As permitted by the authority having jurisdiction.
To adjust stove for operation above 2000 feet the burner orifices may need to be changed.
The orifices are located beneath the log set so it is necessary to first remove the logs.  To do so
please refer to the following  detailed instructions  to achieve optimum performance of your stove.
WARNING ! The following procedure should only be undertaken by a qualified and certified gas
appliance installer.
CAUTION:    DISCONNECT  ANY  ELECTRICAL  CORDS  AND  TURN  OFF  GAS  SUPPLY  TO
UNIT BEFORE PROCEEDING.
 1.
If logset is installed, remove logs and embers at this time.
 2.
With a Phillips screwdriver, remove pilot lighting channel and front log rack.
 3.
Remove the two Phillips head screws that secure the front and rear burner pan in place.
 4.
Remove the burner pans by sliding to the right and lifting out.  (Shutters may need to be
adjusted ‘closed’ to make this easier).
 5.
Slide shutters out of the way.  Using a 3/8" wrench or socket, remove the orifice inserts and
replace with proper orifices for the specified gas.  See below.
6.
Reinstall burner pans and adjust shutters to ‘open’ position.
CAUTION:  The correct orifice placement is critical for proper appliance performance fol-
low  BTU  de-rating  chart  below  to  locate  the  necessary  orifice  size  for  the
front and rear burners.
EQUIVALENT
 
ORIFICE
 
SIZES
 
AT
 
HIGH
 
ALTITUDES
(Includes 4% Input Reduction For Each 1000 Feet)
Orifice size
2000 3000 4000 5000 6000 7000 8000 9000 10000
at Sea Level:
Natural Gas
Front   47
48
48
48
49
50
50
51
51
52
Rear   42
43
43
43
44
44
45
46
47
47
Propane
Front   56
57
57
57
58
58
59
60
61
62
Rear   53
54
54
54
54
54
55
55
55
56