Power Distribution
7.3.6.3
Installation options for 600 mm wide symmetrical racks
Performing the task
Ê
Install the socket strips onto the PDU kit 3 HU as described on 
.
Figure 65: Single-phase 10-way socket strip mounted in a 600 mm wide symmetrical rack
Ê
Install the PDU kit 3 HU into the rack on the desired height.
I
The PDU kit 3 HU has to be installed from HU 7 upwards.
Rack height
Installation direction vertically 
Installation direction horizontally 
42 HU
Not possible
Max. 4x with PDU kit 3 HU
24 HU
Not possible
Max. 4x with PDU kit 3 HU
16 HU
Not possible
Max. 4x with PDU kit 3 HU
Table 18: Installation options for 600 mm wide symmetrical racks