Microcom Technologies Commander General Purpose Variable Speed Drive Gp Manuale Utente

Pagina di 118
Commander GP User Guide
Issue code:   gpxu2
Diagnostics
E-3
Lower
display
No.
Conditions
SEP.diS
180
The UD55 small option module has been removed or is not
fitted correctly.
Perform either of the following:
Ensure a UD55 small option module is correctly fitted
To operate the Drive without a UD55, set parameter 
.00
at 
1000
 and press the 
STOP/RESET
 key.
FSH.Err
182
The memory of the UD55 small option module has been
found to be corrupt.   If the trip has occurred at power-up,
the memory is automatically re-formatted and all the
parameter-sets are erased.   If the trip occurs after power-
up, the memory and parameter-sets are unaffected.   See
the UD55 User Guide.
FSH.Dat
183
No values have been found in the selected parameter-set in
the UD55 small option module.   Consequently, no values
have been copied to the destination Drive.
FSH.TyP
184
The operating mode of the destination Drive  is different
from that related to the selected parameter-set in the
UD55 small option module.   Consequently, no values have
been copied to the destination Drive.   Select an
appropriate parameter-set.
FSH.ACC
185
Write-access to the UD55 small option module has not
been enabled.   Consequently, no values have been copied
to the destination Drive.   To enable write-access, connect
together terminals 40 and 41 on the UD55.
FSH.rng
188
The current rating or voltage rating of the destination
Drive is different from that relating to the selected
parameter-set in the UD55 small option module.  
Consequently, all parameter values have been copied to
the destination Drive except for those listed in Transferring
parameter-sets between Drives of different ratings
 in the UD55
User Guide
.