Burnham Conductivity Controller Dépliant

Pagina di 2
Conductivity Controller
Surface Blowdown Solid State  
Intermittent Sampling
   Controls boiler total dissolved solids (TDS) using  
conductivity measurement and automatic surface  
blowdown via intermittent sampling.
   Adjustable interval timer (1/4 – 3 hours)  
periodically opens an electric valve to sample  
boiler water conductivity.
   If the sample is below the micromhos set point  
on the potentiometer, blowdown is not required  
and the valve will close. If the sample is above  
the micromhos set point on the potentiometer,  
blowdown is required, and the valve will  
remain open.
   Adjustable sample duration timer (10 – 12 minutes)  
again samples to determine if sample is below the  
micromhos set point on the potentiometer to  
permit the valve to close.
   Complete system includes: enclosure, potentiometer,  
two timers and LED lights.
   Valve assemblies purchased separately include:  
solenoid or motor-operated factory-piped valve  
with probe, tee assembly and orifice kit.
   120 VAC, 50/60 HZ, 15 amp.
   Solid state electronics.
   NEMA 4X enclosure.