9 - 72
MELSEC-Q
9   MAJOR POSITIONING CONTROL
(5) An error "No command speed" (error code: 503) occurs if a current speed (-1)
is set in "
Da.8
Command speed".
(6) The software stroke limit check is not carried out when the control unit is set to
"degree".
 Positioning data setting examples
[Setting examples when the reference axis and interpolation axis are designated
as axes 1 and 2, respectively.]
The following table shows the setting examples when "2-axis speed control
(forward run: speed 2)" is set in the positioning data No. 1 of axis 1 (reference
axis).
Axis
Setting item
Axis 1
(reference
axis) setting
example
Axis 2
(interpolation
axis) setting
example
Setting details
Da.1 Operation pattern
Positioning
complete
Setting other than "Positioning complete" is not possible in
speed control.
Da.2 Control system
Forward run
speed 2
Set 2-axis speed control.
Da.3
Acceleration time
No.
1
Designate the value set in " Pr.25  Acceleration time 1" as
the acceleration time at start.
Da.4
Deceleration time
No.
0
Designate the value set in " Pr.10  Deceleration time 0" as
the deceleration time at deceleration.
Da.5
Axis to be
interpolated
1
Set the axis to be interpolated (partner axis).
If the self-axis is set, an error will occur.
Da.6
Positioning address/
movement amount
Setting not required (setting value will be ignored).
Da.7 Arc address
Setting not required (setting value will be ignored).
Da.8 Command speed
6000.00
mm/min
3000.00
mm/min
Set the speed to be commanded.
Da.9 Dwell time
Setting not required (setting value will be ignored).
A
x
is 1   Positioning data N
o
. 1
Da.10 M code
10
Set this when other sub operation commands are issued in
combination with the No. 1 positioning data. (" Pr.18 M
code ON signal output timing" setting only possible in the
WITH mode.)
     Refer to Section 5.3 "List of positioning data" for information on the setting details.