Lightwave Communications Server 3200 Manuale Utente

Pagina di 88
 
7
4.0 Installation 
Instructions 
 
4.1 
Items in the Shipping Container 
 
a) ConsoleServer 3200 user manual 
b) User and Sys Admin Quick Reference Cards 
c) AC power cord 
d) Cable kit part number 200.0135 (four rubber feet included) 
e) ConsoleServer 3200 chassis with installed cards 
 
Additional adapters and cables may also be included in the shipping container if 
ordered.  Large cable and adapter orders are usually shipped in separate containers. 
 
4.1 Rack/Desktop 
Installation 
 
The ConsoleServer 3200 is shipped with 19-inch rack mount 'ears' attached for 
installation in an EIA standard rack. If the unit is to be used in a desktop environment, 
the 'ears' may be removed and four small rubber feet may be installed on the bottom of 
the unit to prevent scratching the desktop and allow airflow through the unit.  Alternate 
sizes of rack mount ‘ears’ are also available. 
 
When mounting the ConsoleServer 3200 in a rack, be sure to allow sufficient space 
behind the unit for cables and adapters. 
 
4.3 
ConsoleServer 3200 Location and Cooling 
 
The ConsoleServer 3200 will operate in a normal equipment room environment without 
any problems. The fan located on the power supply module provides airflow for the 
power supplies, while the majority of cooling relies on convection currents. It is therefore 
necessary to keep the bottom and top of the unit free from obstruction.  Provisions for 
adequate ventilation should be made if the ConsoleServer 3200 is mounted in an 
enclosed rack. 
 
The ConsoleServer 3200 generates 34.1 BTU/hr under normal operation.  Be sure that 
the cooling plant for the machine environment can accommodate the additional heat 
load. 
 
4.4 Power 
Requirements 
 
The ConsoleServer 3200 may operate off AC or DC power, depending on the installed 
power supply module.  The power supply module may be removed and exchanged to 
allow a different power source (AC or DC). 
 
The AC power module is an auto-switching power supply, operating on 110/220 VAC at 
50/60 Hz, and draws approximately 1 A at 110 VAC.  An AC power cord is included with