AIR CONNECTIONS
SUPPLY
Connect air supply to 1/4 NPT port marked "IN." If the above specifications are not met, possibility of internal clogging
exists. Also see MAINTENANCE section.
OUTPUT
Connect output to 1/4 NPT port marked "OUT."
GAUGE
The plugged 1/8 NPT port in the base of the transducer is internally connected with the "OUT" port. A pressure gauge can be
attached to this port to monitor output pressure.
CONTENTS
Air Connections  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 1
Pressure Requirements  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 2
Mounting
 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 2
Direct Mounting
Mounting Kits
Electrical Connections  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 3
Precautions to be observed during installation
Calibration
 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 4
Maintenance  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 5
Agency Approvals, Special Notes, and Cautions  . . . . . . . . . . . . . . . . . .Page 5 & 6
Kits
 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 7
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 8
WARNING
In order to get optimal service from this transducer and ensure warranty coverage the following MUST be followed:
The supply air quality to this instrument must be instrument quality air as defined by ISA Standard 57.0.01-1996.
1. 
Dew point not higher than 35˚F.
2. 
No particulates larger than 3 microns in size.
3. 
Maximum oil content of 1 ppm.
• 
No mechanical adjustments or calibrations are necessary or allowed. All calibration MUST be done with electrical poten-
tiometers on the enclosed circuit board only. See “CALIBRATION” section of instructions for more information.
M-4109/1104 IP510, EP510, IP511, EP511 SERIES
A
3
TABLE 1: SUPPLY PRESSURE REQUIREMENTS
Standard Output
Calibration
0-2 
PSI
0-5 
PSI
0-30
PSI
0-60
PSI
0-100
PSI
0-120
PSI
1-17
PSI
3-9 
PSI
3-15
PSI
3-27
PSI
6-30
PSI
Transducer
Supply Pressure
20-45
PSI
20-45
PSI
50-90
PSI
80-120
PSI
110-130
PSI
130-140
PSI
30-70
PSI
20-100
PSI
20-100
PSI
35-100
PSI
35-100
PSI
)-T1001.qxd  4/11/05  3:23 PM  Page 3