Dacor RV46S Guida All'Installazione
Verifying the Package Contents
• Use and Care Manual
• Anchoring Legs
Installation Planning
A qualified technician must complete the
installation of this appliance. Proper installation
is your responsibility.
Raised Vent System Specifications
Raised Vent
Model No.
For Use with
For Use with Blower
Duct Size
RV30
30” Cooktops
CABP3, REMP3/16
3 1/4”x10”, 8” & 10”
RV36
36” Cooktops
CABP3, REMP3/16
3 1/4”x10”, 8” & 10”
RV46
46” Cooktops
CABP3, REMP3/16
3 1/4”x10”, 8” & 10”
For detailed information on the remote blowers, refer to the Remote Blowers Installation Instructions.
wARNINg:
Failure to disconnect power may
result in electrical shock or fire
hazard! If the electric service
provided does not meet the
product specifications, do not
proceed with the installation. Call
the selling dealer or a licensed
electrician.
Electrical Power Supply
Requirements
It is the owner’s responsibility to ensure that
the electrical connection of this appliance
is performed by a qualified electrician. The
electrical installation, including minimum supply
wire size and grounding, must be in accordance
with the National Electric code ANSI/NFPA 70-
2002* (or latest revision) and local codes and
ordinances.
*A copy of this standard may be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, Massachusetts 02269-9101
The correct 120VAC, 60Hz, 15A circuit must
be supplied for this appliance from a separate,
grounded, circuit that is protected by a properly
sized circuit breaker or time delay fuse.
Duct Planning
wARNINgS
1. To reduce the risk of fire and
to properly exhaust air, ducted
fans must be vented to outside.
Do not vent exhaust air into
spaces within walls, ceilings,
attics, crawl spaces or garages.
2. Improper installation,
adjustment, alteration, service,
or maintenance can cause
personal injury or property
damage.
3. To reduce the risk of fire,
use only ductwork materials
deemed acceptable by state,
municipal and local codes.
NOTES:
NOTES:
1. Best performance is achieved
by using round duct instead of
rectangular, especially when
elbows are required.
2. If multiple elbows are needed,
ensure that there is a minimum
of 24” of straight duct between
any two elbows.
3. Avoid “S” or “back to back”
configurations caused by
adjacent elbows.
4. Thermal breaks, such as a
short section of non-metallic
duct, should be used in areas
of extreme cold.
5. A back-draft damper at the duct
outlet may also be required.
6. Do not use flexible metal duct.
7. Do not use ductwork that is
smaller in cross-sectional area
than the recommended size
duct.
Stiffener Channel Location
RV Overall Dimensions
Front View
30” - RV30
36” - RV36
46” - RV46
36” - RV36
46” - RV46
COOKTOP
8”
26 11/16”
Top Cap
Vent Sleeve
(in raised position)
Countertop
Raised Vent
RV30/36/46
Vent Junction Box
120VAC, 15A, Grounded
Junction Box (not provided)
Support Leg
3 1/4” x 10” Duct
2 1/2”
1 13/16”
1/2”
2 1/4”
1/2”
2”
3”
1/4” min. of flat
3/4”
Overall Dimensions