°F vs. °C Display
The unit is factory configured to display all temperatures in degrees 
Fahrenheit (° F). To switch to degrees Celsius press the ‘Fan Only’ and 
‘Low Fan’ buttons simultaneously for three seconds. The display will show 
a ‘C’ as acknowledgement of the change.  To revert back to ° F press the 
‘Fan Only’ and ‘Low Fan’ buttons simultaneously for three seconds. The 
display will show an ‘F’ as acknowledgement of the change.
Cooling Mode
Pressing the ‘Cool’ button while the unit is in any mode, including off, 
will put the unit into cooling mode. Adjust the temperature readout to the 
desired room temperature and the unit will cycle the compressor on and 
off to maintain a comfortable room. The compressor will come on anytime 
that the room temperature is 1.8° F above the desired temperature. The 
fan operation is dependent on the fan mode selected, either continuous 
or cycling.  See Constant Fan Mode.
Heating Mode
Pressing the ‘Heat’ button while the unit is in any mode, including off, will 
put the unit into heating mode.
Heat Pump Models (PDH)
When the ‘Heat’ button is pressed initially the unit will energize the electric 
resistance heat to quickly bring the room to the set temperature.  When the 
desired room temperature falls 1.8° F below the desired set temperature the 
unit will cycle the compressor on and operate as a heat pump to maintain 
the room temperature while running more efficiently than resistance heat 
only models.  If the room temperature should fall more than 5° F from the 
set temperature the unit will run the resistance heater.  The fan operation 
is dependent on the fan mode selected, either continuous or cycling. Dip 
switch 3 controls the fan mode, see page 23 for setting.  
When the outdoor coil temperature falls below 30° F for more than 2 min-
utes the unit will operate the resistance heaters and not the compressor.  
When the outdoor coil temperature reaches 45° F the compressor will be 
allowed to operate again.
Heat/Cool Models (PDE)
After pressing the ‘Heat’ button, adjust the temperature readout to the 
desired room temperature and the unit will cycle the resistance heat on 
and off to maintain a comfortable room. The heater will come on anytime 
that the room temperature is 1.8° F below the desired temperature. The 
fan operation is dependent on the fan mode selected, either continuous 
or cycling. Dip switch 3 controls the fan mode, see page 23 for setting.
Emergency Heat Operation
In the event of a compressor failure in heat pump mode the compressor may 
be locked out to provide heat through the resistance heater. This feature 
ensures that even in the unlikely event of a compressor failure the room 
temperature can be maintained until the compressor can be serviced. Dip 
switch 1 controls the emergency heat setting, see page 23.
Constant Fan Mode
Pressing the Constant fan mode button will provide constant fan operation 
in cooling or heating modes. The fan speed selection is made by pressing  
either "High" or "Low" fan speed button. 
Cycle/Continuous (Factory Default)
The owner may choose between fan cycling or fan continuous mode 
based on property preference (Note: Even heat monitoring and quiet 
start/stop fan delay only operate in heat mode + cycle mode). Cycle fan 
will conserve energy by only operating the fan when the call for cooling 
or heating is required. 