Maytag MDE18CSAYW Istruzione Sull'Installazione

Pagina di 60
15
DRYER VENTING REQUIREMENTS
1.  Remove red cap from gas pipe on back of dryer.
2.   Connect gas supply to dryer. Use a pipe thread compound 
approved for the type of gas supplied. If flexible metal tubing  
is used, be certain there are no kinks.
If necessary for service, open the toe panel. Use a putty knife  
to press on the toe panel lock located at the center top of the 
toe panel. Pull downward on the toe panel to open. Toe panel  
is hinged at the bottom.
3.   Open the shut-off valve in the gas supply line and make sure 
the dryer has its own gas supply opened.
4.   Test all connections by brushing on an approved noncorrosive 
leak-detection solution. Bubbles will show a leak. Correct any 
leaks found.
Make Gas Connection
GAS SUPPLY CONNECTION
The outside end of main vent should have a sweep elbow directed 
downward. 
If main vent travels vertically through the roof, rather than through 
wall, install a 180° sweep elbow on end of vent at least 2 ft.  
(610 mm) above surface of roof. 
The opening in wall or roof shall have a diameter 1⁄2" (13 mm) 
larger than vent diameter. Vent should be centered in opening.
Do not install screening over end of vent for best performance.
12" min.
(305 mm)*
A main vent can be used for venting a group of dryers. The main 
vent should be sized to remove 5663 l/min. (200 CFM) of air per 
dryer. Large-capacity lint screens of proper design may be used in 
main vent if checked and cleaned frequently. The room where the 
dryers are located should have make-up air equal to or greater than 
CFM of all the dryers in the room.
Back-draft dampers are available from your distributor and should 
be installed in the vent of each dryer to keep exhausted air from 
returning into dryers and to keep exhaust in balance within main 
vent. Unobstructed return air openings are required.
Although usually each single-load dryer should have an 
unobstructed outdoor air opening of 24 in.
2
 (154 cm
2
) (based  
on 1 in.
2
 [6.5 cm
2
] per 1,000 Btu [252 kcal]), common make-up air 
openings are also acceptable. Set up common openings so  
the make-up air is distributed equally to all of the dryers. Keep  
in mind that the coverage area must be increased by 33% to 
account for the use of registers or louvers over the openings.  
Also, make-up air openings should not be installed near the 
location where exhaust vents exit the building.
Each vent should enter the main vent at an angle pointing in  
the direction of the airflow. Vents entering from the opposite side 
should be staggered to reduce the exhausted air from interfering 
with the other vents.
The maximum angle of each vent entering the main vent should be 
no more than 30°.
Keep air openings free of dry cleaning fluid fumes. Fumes create 
acids which, when drawn through the dryer heating units, can 
damage dryers and items being dried.
A clean-out cover should be located on the main vent for periodic 
cleaning of the vent system.
If an Exhaust Hood Cannot be Used
Multiple Dryer Venting
24" min.
(610 mm)
* Minimum clearance above any 
accumulation of snow, ice, or 
debris such as leaves
30˚ max.
air flow
Air Flow