OceanAire PAC6012 Guida Dello Sviluppatore

Pagina di 32
STANDARD FEATURES 
CABINET 
 
The AirBoss Series cabinet is constructed of 18 gauge steel with a gray polyester powder 
coated finish that will compliment any decor. The entire cabinet is insulated with a sound- 
absorbing insulation for cool, quiet comfort.  All units come equipped with handles and 
swivel casters for portability and convenient set-up. 
 
ELECTRONIC THERMOSTAT 
 
All Air Boss unit are equipped with a non-programmable electronic thermostat.  When 
power is connected to the unit, the thermostat will control the Air Boss to cool a space to 
the desired temperature.  The thermostat is also capable of controlling the fan to operate 
automatically (when needed) or continuously.  To protect the compressor from short-
cycling, there is a built-in, 4-minute time delay in the thermostat.   
 
FAN SPEED CONTROL 
 
A two position rocker switch, located next to the thermostat, provides the user with the 
option of running the evaporator fan in high-speed or low-speed. 
 
CONDENSATE RESERVOIR/PUMP 
 
Air Boss units come equipped with a means for handling the condensate generated dur-
ing the cooling process.  All models except the 5-ton models come equipped with a 
Condensate Reservoir Tank, that captures the condensate from cooling.  The tank can 
then be easily removed from the unit and emptied as required.   
 
The 5-ton Air Boss models come equipped with an Automatic Condensate Pump that 
disposes of the condensate.  The pump comes with a 25 foot long vinyl hose that allows 
for the disposal of the condensate water to a drain.  The automatic pump is capable of a 
20ft lift, to handle just about any installation requirement. 
 
CONDENSATE ALARM LIGHT 
 
On the front of all Air Boss models, there is a Condensate Alarm Light (RED) located near 
the thermostat.  For models less than 5-tons, the light indicates that the condensate tank 
is full and needs to be emptied. In the 5-ton Air Boss units (model PAC60) the light indi-
cates a condensate pump over-flow condition where the pump is either disabled, or inca-
pable of rejecting the condensate water, and must be serviced. 
 
FILTERS 
 
All Air Boss units are equipped with washable filters at the air intakes. 1/8” mesh air filters 
located behind the evaporator return air grill serve to filter the air before it is cooled.  A 
1/2” aluminum mesh filter serves to protect the condenser coil from dust build-up.  Both 
filters can be easily removed and cleaned. 
 
HIGH PRESSURE SAFETY SWITCH 
 
Located on the back of the Air Boss unit is a manual re-set high pressure switch, used for 
the protection of the compressor. If the condensing pressure exceeds the limit setting, the 
cut-out shuts down the compressor, while the evaporator fan remains running.  The com-
pressor can be re-started, once the condensing pressure has lowered, by depressing the 
“RESET” button.  
 
POWER CORDS 
 
All Air boss units come with power cords, convenient connection and portability.  All units 
except the 5-ton models, and 3-phase models are equipped with LCDI for added safety 
devices.