OceanAire 2OACH3634 Manuale
Plenum Kit
Duct/Flange
2OACH12
2OACH18 2OACH24 2OACH36 2OACH60
FILTERS
DEP-10
10 inch
(1) 10”X20”X1”
2DEP-12
12 inch
(1) 15”X25”X1”
DEP-16
16 inch
(1) 12”X30”X1”
(1)15”X30”X1”
Maximum
Equivalent
Feet
25
50
50
50
100
Est. External
Static
Pressure
(.20)
(.25)
(.25)
(.25)
(.50)
ACCESSORIES
EVAPORATOR RETURN AIR PLENUM, 2DEP
Evaporator return air plenums are available for installations where it is required to duct air to
the inlet of the evaporator. The evaporator return air plenums allow the user to connect
round duct (flexible or rigid) to the return air intake to reduce air noise and increase the
number of options for solving difficult cooling problems. The plenum attaches to the front of
the unit, replacing the return air grill. Refer to the table below for configuration and applica-
tion information
the inlet of the evaporator. The evaporator return air plenums allow the user to connect
round duct (flexible or rigid) to the return air intake to reduce air noise and increase the
number of options for solving difficult cooling problems. The plenum attaches to the front of
the unit, replacing the return air grill. Refer to the table below for configuration and applica-
tion information
DEP-10 for 2OACH12
transitions the return air opening to 10-inch round duct.
2DEP-12 for 2OACH18 & 2OACH24
transitions the return opening to a 12-inch round duct.
DEP-16 for 2OACH36, 60
transitions the return opening to a16-inch round duct.
NOTE—When a evaporator return air plenum is installed, it is recommended to set the
evaporator blower speed to high, to avoid evaporator freeze-up.
evaporator blower speed to high, to avoid evaporator freeze-up.
FILTER(S)
2DEP—EVAPORATOR
RETURN AIR PLENUM
RETURN AIR PLENUM