F4:  Overheat protection for exhaust temperature
Yes
Electrify the machine again and turn it on with
the remote controller, then measure the 
temperature at the exhaust temperature 
sensor of the compressor on the outdoor unit
and check whether the temperature exceeds 
110
shortly after the machine starts up
ć
Measure the temperature at the 
exhaust temperature sensor of the 
compressor on the outdoor unit and 
Malfunctions occur after running for 
some time even though the measured
temperature is below 110
ć.
Pull out the exhaust sensor and measure its 
resistance at standard temperatures. Check
whether the results deviate much from those 
in the resistance-temperature table
1) The cryogen may have 
been leaked during 
installation, or there may 
be leakage in the piping 
system.
2) There may be other 
causes to make the 
exhaust temperature too 
high.
Exhaust temperature 
sensor is broken and 
needs be replaced
The sensor is damaged.
Replace the sensor with a 
new one.
No
No
Yes
Yes
The outdoor mainboard is 
damaged and needs be 
replaced
No