Installation Instructions
SPECIFICATIONS
Dimensions:  Width: 12.5” cabinet, 13” with doors 
Height: 14.5” cabinet, 17” with 2.5” leveling feet 
Length: 22” cabinet, 27” with collars
Weight: 65 lbs.
Capacity:  65 pints/day @ 150 cfm 
AHAM DH-1-2003 80°F, 60% RH conditions
Efficiency:  1.8 Liters per kilowatt hour 
AHAM DH-1-2003 80°F, 60% RH conditions
Power:  115VAC, 60 Hz, 8A Operating Current 
Unit equipped with 8 ft. grounded power cord 
Dedicated 15 Amp circuit recommended
Airflow: 
 
 
 
Inlet Air Operating Conditions: 60°F to 95°F, 30% RH to 99% RH 
Installation Conditions: 40°F to 140°F, 0% RH to 99% RH
Evaporator Frost Sensor:  25°F +/- 5°F, circuit opens (cut-out) 
55°F +/- 5°F, reset temperature (cut-in)
Filter: MERV 8, washable
Dehumidistat Control Accuracy: +/- 6%RH with +/-6% Differential
 WARNING
1.  120 volts may cause serious injury from electric shock. Disconnect electrical power 
before starting installation. Leave power disconnected until installation is complete.
2.  Sharp edges may cause serious injury from cuts. Use care when cutting plenum 
openings and handling ductwork.
3.  Dropping may cause personal injury or equipment damage. Handle with care.
4.  Do not remove the inlet or outlet screen. Both screens are required to protect from 
moving parts and electrical components. 
 CAUTION
1.  Do not use in pool applications.
2.  If unit has been shipped or stored on 
its side, wait 24 hours before running.
3.  Do not use solvents or cleaners on or 
near the circuit board.
P ("w.c.)
Airflow (cfm)
0
230
0.25
190
0.50
150
LOCATION CONSIDERATIONS
1. 
 Install Unit Indoors: Do not expose to elements.
2. 
 Drain Accessibility: If a drain is not located in the 
installation area, a condensate pump may be required.
3. 
 Power: Dedicated outlet within 8 feet of unit.
4. 
 Filter Access: Allow for 12” clearance on one side of 
the unit for removal of filter. (
Figure 1)
5. 
 Inlet: If inlet is not ducted, a minimum of 6” of open 
space is required from the inlet panel to an adjacent 
surface.
TOP VIEW
FILTER
12" MINIMUM CLEARANCE
      FOR FILTER
      (EITHER SIDE)
6" MINIMUM CLEARANCE
FOR PROPER AIR FLOW
90-1426
FIGURE 1 – Filter 
Access Clearance
UNPACKING AND CONTENTS
Do not tip unit to remove from carton.
1.  Open carton completely using cut line shown along bottom 
perimeter of carton.
2.  Remove all cardboard inner pack (top edges and duct collars).
3.  See 
Figure 2 for opening view and contents. 
a. Installation Manual 
b. Owner’s Manual 
c. Dehumidistat (mounted to inlet panel) 
d. Bag with Dehumidistat Cover Plate, Screws (2), Anchors (2) 
e. Outlet with Back Flow Damper 
f.  8 ft. Grounded Power Cord 
g. Wiring Access Panel
a b
c
d
e
f
g
FIGURE 2 – Carton 
Opening & Contents