SECO-LARM USA EAP-5D1 Dépliant

Pagina di 1
AC power failure supervision relay.
Battery failure supervision relay.
Selectable 2.2K-Ohm End-of-Line (EOL) resistor for AC failure 
and battery failure supervision relays.
Selectable delay timer (5 sec., 5 min., 5 hours) for AC failure 
supervision relay.
LED overload indicator and automatic shutdown for short-
circuit protection.
Over-current fuse-protected AC input.
Built-in back-up battery charger
Automatically switch to back-up battery if AC fails.
Individual AC input and DC output LED status indicators.
      
1.949.261.2999 (CA & Int’l)      1.800.662.0800      Fax: 1.949.261.7326
Email: info@seco-larm.com      Website: www.seco-larm.com 
16842 Millikan Avenue, Irvine, CA  92606 
AccessControlPowerSupply.cdr
Features:
Field selectable  for 12VDC or 24VDC output.
Operating voltage input 110~240 VAC.
Adjustable voltage range (11~15 VDC, 23~26 VDC) to 
compensate for voltage drop.
Supply current: 5 Amps @ 12VDC, 4.5 Amps @ 24VDC.
AC input fuse rating 3.15 Amps (glass fuse).
DC output overload sensing with red LED indicator and 
automatic shutdown during short circuit.
Power
Heavy-duty steel case to protect the power connections.
Removable steel cover for easy access.
Ventilation holes to prevent heat build-up.
Enclosure has enough room for two 7AH batteries.
6-foot power cord and battery leads included.
Dimensions: 12-3/16” x 12-7/16” x 3-9/16”.
Knock-out on the cover for optional cam lock.
Enclosure
Dimensions: 12-3/16" x 12-7/16" x 3-9/16"
®
EAP-5D1
1 Output, 5A@12VDC, 4.5A@24VDC
The SECO-LARM policy is one of continual development.  For that reason, SECO-LARM reserves the right to change prices and specifications without notice. SECO-LARM is not responsible for misprints.
Copyright 2007 SECO-LARM U.S.A., Inc. All rights reserved.
Connections:
DIP switch 
for 12 or 24 VDC 
output selection
VR1 rotary knob 
for DC output 
voltage range 
adjustment
AC failure 
delay timer 
DIP switch
End-of Line 
(EOL) 2.2K Ohm 
resistor DIP switch
AC input fuse
AC input LED
status indicator
SL-126A
Power Supply
DC output LED 
status indicator*
Back-up 
battery terminal
AC failure Supervision 
Relay Output to 
Audio/Visual 
warning device
Battery failure & low battery 
Supervision Relay Output to
Audio/Visual warning device
DC output 
 terminal block
12 VDC Battery
(Optional)
+
-
Power Supply
Battery presence
and low battery
monitor DIP switch
110~240 VAC
INPUT