Honeywell R0512 Manuale Utente

Pagina di 86
EXCEL 50/100/500/600/800 
DATA POINTS 
 
 
EN2B-0092GE51 R0512 
11 
•  Pseudo analog points 
•  Pseudo digital points 
•  Pseudo totalizer inputs 
•  Pseudo point multistage 
 
 
Pseudo analog points 
Pseudo analog points are software points containing an analog value in the user 
program. A pseudo analog point could, for example, contain a flow temperature 
setpoint calculated from the room setpoint and the outside air temperature via the 
heating curve. 
 
 
Pseudo digital points 
Pseudo digital points are software points containing a digital value in the user 
program. 
 
For example, logical AND operation. 
The AND operation provides a logical 1 output when all input conditions are also 
logical 1. Otherwise the output is a logical 0. If the user program contains such an 
AND operation on different input conditions, then the output could be available as a 
pseudo digital datapoint. 
 
 
Pseudo totalizer inputs 
Pseudo totalizer inputs are digital software points from the user program, where a 
totalizer counter input is recorded 

 
Pseudo point multistage 
Pseudo point multistage datapoints are identical to flexible datapoint of the type 
"multistage" except that they allow for 16 stages (including the “off stage“) and the 
attribute "Status Text" allows for 16 status texts to be attached. The attribute "Tech-
nical Address" is not required. 
 
 
Global Datapoints 
If your control and monitoring system contains more than one controller, the con-
trollers communicate with one another via the system bus. Any given controller can 
thus both receive (read) datapoints from other controllers and transmit datapoints to 
other controllers. Such datapoints are referred to as global datapoints
 
NOTE:
  The term “global” as used here encompasses more than just those points 
explicitly labeled as “global” in the CARE engineering tool. 
 
Global datapoints which a controller receives (reads) from other controllers are 
referred to as local global datapoints, and global datapoints which a controller 
transmits to other controllers are referred to as remote global datapoints. 
During CARE engineering, the program engineer must take care that he does not 
exceed the maximum allowed 256 global datapoints (remote and local) per 
controller. 
 
C
SYSTEM BUS
LON
 
Fig. 4. Global datapoints are available to all controllers on the system bus