TROUBLESHOOTING
Continued
OBSERVED PROBLEM
Moisture/condensation noticed 
on windows
Heater  produces  a  whistling 
noise when burners are lit
White powder residue forming 
within burner box or on adjacent 
walls or furniture
Remote does not function
Fireplace produces a clicking/
ticking noise just after burner 
is lit or shut off
POSSIBLE CAUSE
1. Not enough combustion/ven-
tilation air
1. Turning control knob to HI po-
sition when burners are cold
2. Air in gas line
3. Air  passageways  on  heater 
blocked
4. Dirty  or  partially  clogged 
burner orifice(s)
1. When  heated,  vapors  from 
furniture polish, wax, carpet 
cleaners,  etc.  may  turn  into 
white powder residue
1. Battery is not installed. Battery 
power is low
1. Metal expanding while heating 
or contracting while cooling
REMEDY
1. Refer to Air for Combustion 
and Ventilation requirements 
(page 5)
1. Turn control knob to LO po-
sition and let warm up for a 
minute
2. Operate  burners  until  air  is 
removed from line. Have gas 
line checked by local natural  
or propane/LP gas company
3. Observe minimum installation 
clearances (see page 9)
4. Clean burners (see  Cleaning 
and Maintenance, page 23) or 
replace burner orifice(s)
1. Turn  heater  off  when  using 
furniture polish, wax, carpet 
cleaners, or similar products
1. Replace  9-volt  batteries  in 
receiver and remote control
1. This is common with most heat-
ers. If noise is excessive, contact 
qualified service person