CAUTION: Do not stop operation by switching OFF electromagnetic contactors on the 
primary or secondary sides of the inverter. 
When there has been a sudden power failure while an operation instruction is active, then 
the unit may restart operation automatically after the power failure has ended. If there is 
a possibility that such an occurrence may harm humans, then install an electromagnetic 
contactor (Mgo) on the power supply side, so that the circuit does not allow automatic 
restarting after the power supply recovers. If the optional remote operator is used and the 
retry function has been selected, this will also cause automatic restarting when a Run 
command is active. So, please be careful.
CAUTION: Do not insert leading power factor capacitors or surge absorbers between 
the output terminals of the inverter and motor. 
CAUTION: MOTOR TERMINAL SURGE VOLTAGE SUPPRESSION FILTER 
(For the 400 V CLASS)
In a system using an inverter with the voltage control PWM system, a voltage surge 
caused by the cable constants such as the cable length (especially when the distance 
between the motor and inverter is 10 m or more) and cabling method may occur at the 
motor terminals. A dedicated filter of the 400 V class for suppressing this voltage surge 
is available. Be sure to install a filter in this situation.
Power 
Input
Inverter
L1, L2, L3
Ground fault 
interrupter
U, V, W
Motor
PCS
FW
Power 
Input
Inverter
L1, L2, L3
Ground fault 
interrupter
U, V, W
Motor
GND lug
Surge absorber
Leading power 
factor capacitor