Hitachi L200 Manuale Utente

Pagina di 280
L200 Inverter
Oper
ations
and Monitor
ing
4–43
The alarm relay output can be configured in two main ways: 
• Trip/Power Loss Alarm – The alarm relay is configured as normally closed 
(C036=1) by default, shown below (left). An external alarm circuit that detects broken 
wiring also as an alarm connects to [AL0] and [AL1]. After powerup and short delay 
(< 2 seconds), the relay energizes and the alarm circuit is OFF. Then, either an inverter 
trip event or an inverter power loss will de-energize the relay and open the alarm 
circuit.
• Trip Alarm – Alternatively, you can configure the relay as normally open (C036=0), 
shown below (right). An external alarm circuit that detects broken wiring also as an 
alarm connects to [AL0] and [AL2]. After powerup, the relay energizes only when an 
inverter trip event occurs, opening the alarm circuit. However, in this configuration, an 
inverter power loss does not open the alarm circuit.
Be sure to use the relay configuration that is appropriate for your system design. Note 
that the external circuits shown assume that a closed circuit = no alarm condition (so that 
a broken wire also causes an alarm). However, some systems may require a closed 
circuit = alarm condition. In that case, then use the opposite terminal [AL1] or [AL2] 
from the ones shown.
N.C. contacts (C036=01)
N.O. contact (C036=00)
During normal operation
When an alarm occurs 
or when power is OFF
During normal operation 
or when power is OFF
When an alarm occurs
AL0
AL2
AL1
Power
supply
Alarm
device
AL0
AL2
AL1
Power
supply
Alarm
device
AL0
AL2
AL1
Power
supply
Alarm
device
AL0
AL2
AL1
Power
supply
Alarm
device
Power
Run 
Mode
AL0–
AL1
AL0–
AL2
ON
Normal
Closed
Open
ON
Trip
Open
Closed
OFF
Open
Closed
Power
Run 
Mode
AL0–
AL1
AL0–
AL2
ON
Normal
Open
Closed
ON
Trip
Closed
Open
OFF
Open
Closed