L200 Inverter Specifications
Getting Star
ted
1–6
Footnotes for the preceding table and the tables that follow: 
Note 1:
The protection method conforms to JEM 1030.
Note 2:
The applicable motor refers to Hitachi standard 3-phase motor (4-pole). When 
using other motors, care must be taken to prevent the rated motor current (50/
60 Hz) from exceeding the rated output current of the inverter.
Note 3:
The output voltage decreases as the main supply voltage decreases (except 
when using the AVR function). In any case, the output voltage cannot exceed 
the input power supply voltage.
Note 4:
To operate the motor beyond 50/60 Hz, consult the motor manufacturer for 
the maximum allowable rotation speed.
Note 5:
When using the inverter with 3-phase power input, remove the single phase 
filter and install a 3-phase filter with the appropriate ratings.
Note 6:
 For achieving approved input voltage rating categories:
• 460 to 480 VAC – Over-voltage Category 2 
• 380 to 460 VAC– Over-voltage Category 3
To meet the Over-voltage Category 3, insert an EN or IEC standard compliant 
isolation transformer that is earth grounded and star connected (for Low 
Voltage Directive).
Note 7:
At the rated voltage when using a Hitachi standard 3-phase, 4-pole motor.
Note 8:
The braking torque via capacitive feedback is the average deceleration torque 
at the shortest deceleration (stopping from 50/60 Hz as indicated). It is not 
continuous regenerative braking torque. The average deceleration torque 
varies with motor loss. This value decreases when operating beyond 50 Hz. If 
a large regenerative torque is required, the optional regenerative braking 
resistor should be used.
Note 9:
The frequency command is the maximum frequency at 9.8V for input voltage 
0 to 10 VDC, or at 19.6 mA for input current 4 to 20 mA. If this characteristic 
is not satisfactory for your application, contact your Hitachi sales representa-
tive.
Note 10: If the inverter is operated outside the region shown in the graph to the right, 
the inverter may be damaged or its service life may be shortened. Set B083 
Carrier Frequency Adjustment in accordance with the expected output current 
level.
Note 11: The storage temperature refers to the short-term temperature during transport.
Note 12: Conforms to the test method specified in JIS C0040 (1999). For the model 
types excluded in the standard specifications, contact your Hitachi sales
representative.
Carrier frequency
Rated 
current
100%
14.0
0
70%
5.0
Derating Curve
Operating region
Curve at 40
°
C
kHz