Hitachi L200 Manuale Utente

Pagina di 280
“A” Group: Standard Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–18
Be aware that running the motor at a low speed for a long time can cause motor 
overheating. This is particularly true when manual torque boost is ON, or if the motor 
relies on a built-in fan for cooling.
NOTE: Manual torque boost applies only to constant torque (A044=00) and variable 
torque (A044=01) V/f control.
Voltage Gain – Using parameter A045 you 
can modify the voltage gain of the inverter (see 
graph at right). This is specified as a percent-
age of the full scale output voltage. The gain 
can be set from 20% to 100%. It should be 
adjusted in accordance with the motor specifi-
cations.
The following table shows the methods of 
torque control selection.
V
100%
20%
Hz
Voltage Gain
0
A045
“A” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF 
(EU)
–FU 
(USA)
Units
A041 Torque boost select
Two options:
00... Manual torque boost
01... Automatic torque boost
00
00
%
V-Bst Slct    MN
A241 Torque boost select, 2nd 
motor
Two options:
00... Manual torque boost
01... Automatic torque boost
00
00
%
2VBst Slct    MN
A042 Manual torque boost 
value
Can boost starting torque 
between 0 and 20% above 
normal V/f curve,
range is 0.0 to 20.0%
5.0
5.0
%
V-Bst V  0005.0%
A242 Manual torque boost 
value, 2nd motor
Can boost starting torque 
between 0 and 20% above 
normal V/f curve,
range is 0.0 to 20.0%
0.0
0.0
%
2VBst V  0000.0%
A043 Manual torque boost 
frequency adjustment
Sets the frequency of the V/f 
breakpoint A in graph (top of 
previous page) for torque 
boost, range is 0.0 to 50.0%
3.0
3.0
%
M-Bst F  0003.0%
A243 Manual torque boost 
frequency adjustment, 
2nd motor
Sets the frequency of the V/f 
breakpoint A in graph (top of 
previous page) for torque 
boost, range is 0.0 to 50.0%
0.0
0.0
%
2MBst F  0000.0%
A044 V/f characteristic curve 
selection
Two available V/f curves;
three select codes:
00... Constant torque
01... Reduced torque
02
02
CTRL       C-TRQ