(2)  Selection of the rated sensitivity current for the earth (ground) leakage circuit
breaker
When using the earth (ground) leakage circuit breaker with the inverter circuit, select its rated sensitivity
current as follows, independent of the carrier frequency setting:
<Example>
• Breaker for harmonic and surge: 
Rated sensitivity current: 
l
 10 
×
 (lg
1
 + lgn + lg
2
 + lgm)
• Standard breakers:
Rated sensitivity current: 
l
 10 
×
 {lg
1
 + lgn + 3 ( (lg
2
+lgm)}
lg
1
, lg
2
:leakage currents of cable path 
during commercial power supply operation
lgn*:    leakage current of noise filter on 
inverter input side
lgm:    leakage current of motor during 
commercial power supply operation
Note: 1. The NV should be installed to the 
primary (power supply) side of the 
inverter.
2. Earth (Ground) fault in the secondary 
side of the inverter can be detected at 
the running frequency of 120Hz or 
lower.
3. In the 
 connection neutral point 
earthing (grounding) system, the 
sensitivity current is purified against an 
earth (ground) fault on the inverter 
secondary side. Earthing (grounding) 
must be conform to the requirements 
of national and local safety regulations 
and electrical code. (JIS, NEC section 
250, IEC 536 class 1 and other 
applicable standards)
Breaker for 
harmonic and surge
Standard breakers
Leakage current Ig1 (mA)
33 
×
5m
= 0.17
1000m
Leakage current Ign (mA)
0 (without noise filter)
Leakage current Ig2 (mA)
33 
×
70m
= 2.31
1000m
Motor leakage current Igm 
(mA)
0.18
Total leakage current (mA)
2.66
7.64
Reted sensitivity current (mA)
Ig 
×
 10)
30
100
4. When the breaker is installed on the secondary side of the inverter, it may be unnecessarily operated by
harmonics if the effective value is less than the rating. In this case, do not install the breaker since the
eddy current and hysteresis loss increase, leading to temperature rises.
5. The following models are standard breakers. . . . . . . . . . . . . . . . . .BV-C1, BC-V, NVB, NV-L, NV-G2N, NV-
G3NA, and NV-2F type, leakage current
relays (except for NV-ZHA), NV with AA
neutral wire open-phase protection
The following models are breakers for harmonic and surge. . . . . .NV-C/NV-S/MN series, NV30-FA, NV50-
FA, BV-C2, leakage current alarm
breaker (NF-Z), NV-ZHA, NV-H
*  Be careful of the leakage current value of the noise filter installed on the inverter input side.
(Refer to the FR-A500 catalog for details of Mitsubishi inverter dedicated filter.)
0
20
40
60
80
100
120
2 3.5
5.5
8 14 22
30
38
60
80
100
150
0.1
1.5
3.7
2.2
7.5 15 22
11
37
30
55
45
0.2
0.3
0.5
0.7
1.0
2.0
5.5
18.5
Leakage current example
of 3-phase induction motor
during commercial power
supply operation
(200V 60Hz)
Le
akage
 cur
ren
(mA
)
Le
akage
 cur
ren
(mA
)
Cable size (mm  )
2
Motor capacity (kW)
Example of leakage current 
per 1km in cable path during 
commercial power supply
operation when the CV 
cable is routed in metal 
conduit (200V 60Hz)
NV
Ig1
Ign
Ig2
Igm
IM
Inverter
Noise
filter
5.5mm
2
×
5m
5.5mm
2
×
70m
3
φ
200V 2.2kW