"UniVert 2" inverter 
 
Page 31 of 42 
8000012364 BAL, en 
8 Technical 
Data 
8.1 
General Data INV 
DC input current ............................ < rated input current 
DC fuse required ........................... gL 80 A with type 3.3 kVA 48 V 
gL 63 A with type 3.3 kVA 60 V 
gL 20 A with type 3.3 kVA 220 V 
gL 80 A with type 1.5 kVA 24 V 
gL 36 A with type 1.5 kVA 48 V 
gL 32 A with type 1.5 kVA 60 V 
gL 25 A with type 2.5 kVA 110 V 
Manufacturing and type test .......... In acc. with DIN 60146 Part 1-1 
Emitted interference in acc. with EN 50081-1 
- Conducted interference  .............. In acc. with EN 55022 Class "B" 
- Emission ...................................... In acc. with EN 55022 Class "B" 
Noise immunity in acc. with EN 50082-2 
- Housing ....................................... ESD test to EN 61000-4-2, 
6 kV contact 
HF field to EN 61000-4-3, 
10 V/m (30 MHz – 1 GHz) 
- Power cables ............................... Burst test in acc. with 
EN 61000-4-4, 2 kV 
Surge test in acc. with 
EN 61000-4-5, 
2 kV asymmetrical 
- Control cables ............................. Burst test in acc. with 
EN 61000-4-4, 2 kV 
Surge test in acc. with 
EN 61000-4-5, 
2 kV asymmetrical 
Functional extra-low voltage .......... With safe isolation at UO ≤ 60 V DC 
to VDE 0100 Part 410 11.83 
Section 4.3.2 
Dynamic response .........................
≤ 3% with sudden load fluctuations 
between 0%-100%-0% rated 
output current 
Overload behaviour ....................... 1.6 x rated current for 1 minute 
1.3 x rated current for 10 minutes 
Short-circuiting............................... Continued short-circuit-proof