Supplemental Installation Information for APC Chillers
5
Dual Power Feature (Optional)
The optional dual power feature provides a separate power connection point for the pumps and 
controls. If the circuit is connected to an Uninterruptible Power Supply (UPS), the power connection 
keeps the pumps running to recirculate cooling water in the event of a power failure.
Upon loss of power, all compressors and fans shut down. At the same time, the dual-power relay 
closes, putting the unit in heat mode, allowing the controller to keep the pumps running and also 
removes any call for cooling.
On power restoration, the dual power relay opens. The unit returns to cooling mode and stages up 
compressors as required.
See the electrical schematics included in this packet containing electrical data on the power feeds for 
the pumps and chiller.