Honeywell F74C Manuale Utente

Pagina di 8
F74C REVERSE RINSING FILTER; MV876 AUTOMATIC-BACKWASH CONTROLS
3
62-0165
Table 2. Flow Capacity of F74C in Gallons per Minute (gpm).
Table 3. MV876B Timer Selections.
Planning the Installation
The F74C should be sized based on the required flow 
rate and the resulting pressure drop across the filter. As a 
guideline for most applications, the F74C should be sized 
for a  pressure drop between 3 psi and 7 psi.
EXAMPLE: What size F74C is required to provide a flow 
rate of 20 gpm? Reading Table 2 at 20 gpm, a 3/4 in. 
model has 5 psi drop and a 1 in. model has 4 psi drop. 
As both models meet the 3 to 7 psi range, the selection 
should be based on size preference. 
An increased pressure drop across the filter results when 
higher velocities are maintained to increase the capacity 
through any given size filter. Severe pressure drops will 
be encountered as capacity approaches that of the pipe 
size. To ensure the backwash cycle operates properly 
and cleaning action is not reduced, follow all 
recommendations in Fig. 3. Refer to Fig. 3a for an ideal 
installation.
All filter installations are different. The size, type and 
amount of dirt and debris and the flow rate must always 
be considered when choosing a screen and deciding to 
install multiple F74C Water Filters in parallel.
Fig. 3. Ideal F74C installation. A funnel
 mounted directly under the backwash
 port is the best installation layout.
Fig. 4. Make sure the inlet pipe 
is not downsized.
Fig. 5. Make sure the backwash outlet pipe
 is not downsized, long or crimped. Instead,
 install a short oversized pipe on the backwash 
outlet. Do not use a low capacity solenoid 
valve to automate the backwash cycle.
Model
Size
Pressure Drop in psi
Cv
2
3
4
5
15
F74C1015
3/4
9.0
12.7
15.6
18.0
20.1
34.9
9
F74C1023
1
10.1
14.3
17.5
20.2
22.6
39.1
10.1
Program Value
Backwash Interval
1
4 minutes
2
8 minutes
3
16 minutes
4
32 minutes
5
1 hour
6
2 hours
7 4 
hours
8
8 hours
9
17 hours
10
34 hours
11
3 days
12
6 days
13
11 days
14
23 days
15
45 days
16 3 
months
M17705
M17706
M17707
62-0165.fm  Page 3  Wednesday, June 20, 2007  9:21 AM