Greenheck Fan SMD-401 Manuale Utente

Pagina di 4
Model SMD-401 meets the requirements for smoke 
dampers established by:
National Fire Protection Association
    NFPA Standards 92A, 92B, 101 & 105
IBC  International Building Codes
New York City (MEA listing #260-91-M)
California State Fire Marshall
     Listing#: 3230-0981:108 (smoke)
“UL CLASSIFIED (see complete marking on 
product)”
“UL CLASSIFIED to Canadian safety standards 
(see complete marking on product)”
 
Standard 555S (Listing #R13317)
APPLICATION
Model SMD-401 is a class I leakage rated smoke damper. High strength, 
streamlined extruded airfoil blades insure lowest resistance to airflow in 
HVAC systems with velocities to 3000 fpm  (15.2 m/s) and 6 in. wg (1.5 
kPa). Model SMD-401 may be installed vertically (with blades running 
horizontal) or horizontally and is rated for airflow and leakage in either 
direction.
RATINgS
 
Leakage: 
UL 555S leakage class I. Leakage 
 
 
rated in both directions 
 
Velocity:  
Operational rated to 3000 fpm 
 
 
(15.2 m/s) for sizes up to  
 
 
48 in. W x 108 in. H or 144 in. H x 36 in. H  
 
 
(1219mm x 2743mm) or  
 
 
(3658mm x 914mm) or 
 
 
2000 fpm (10.2 m/s) for sizes 
 
 
greater than that. Rating is for 
 
 
airflow in either direction through 
 
 
damper. 
 
Temperature: 
250°F (121°C) with all actuators. 
 Maximum Pressure: 
6 in. (1.5 kPa)
STANDARD CONSTRUCTION
 
Frame:  
5 in. x 1 in. (127mm x 25mm) 
 
 
galvanized steel hat channel with 
 
 
reinforced corners. A low profile 
 
 
head and sill are used on sizes less 
 
 
than 17 in. (432mm) high to 
 
 
maximize free area and  
 
 
performance. 
 
Blades:  
Airfoil shape constructed of heavy 
 
 
gauge extruded aluminum. 
 
 
Structural reinforcement through 
 
 
the entire length. 
 
Seals: 
Extruded silicone rubber blade 
 
 
seals. Flexible stainless steel jamb seals. 
 
Linkage: 
Concealed in jamb. 
 
Axles: 
1
2
 in. (13mm) dia. plated steel. 
 
Bearings: 
Bronze sleeve type
SIzE LIMITATIONS:
 
Minimum Size: 
8 in. W x 8 in. H (203mm x 203mm) 
 
Maximum Size: 
 
Single Section: 
48 in. W x 60 in. 
 
 
(1219mm W x 1524mm H) 
 
Multiple Section: 
192 in. W x 72 in. H 
 
 
(4877mm W x 1829mm H) or  
 
 
48 in. W x 288 in. H 
 
 
(1219mm W x 7315mm H) or 
 
 
384 in. W x 36 in. H 
 
 
(9754mm W x 914mm H)
Optional Features:
• Galvanized steel sleeves 
• Stainless steel bearings 
• OCI (Open closed indication switches) 
• Electric or pneumatic actuators to accomplish smoke 
  management and system functions. 
• POC retaining angles  
• Smoke detector 
• Momentary switch 
• Transformer
Model SMD-401
Smoke Dampers
 
Extruded Airfoil Blades
UL 555S Leakage Class I
*W&H dimensions furnished approximately 
1
/
4
 in. (6mm) undersize.
(Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.
H*
W*
LH
RH
Installation instructions available at www.greeenheck.com