Maytag ERV-150 Manuale Utente
23
8.0
Installation of the Controls
(cont’d)
4- Connect the wires to the main control.
(See figure 17.)
5- Make sure the instruction pull-out is in the
occupant’s language. If not, turn it to the other side.
(See figure 18.)
(See figure 18.)
6- Reinstall the cover plate and the button(s).
7- Connect the wires to their corresponding position inside the
electrical compartment. Make sure the connections of the unit
and of the wall control correspond exactly. (See figure 19.)
and of the wall control correspond exactly. (See figure 19.)
8- Connect the optional control (if applicable) by referring to Section 8.3.
9- Do the appropriate connection to the furnace (if applicable) by referring to Section 8.4.
10- NOTE: If the unit is installed in a cold region (Zone A, as defined in Section 3.0), set up “extended
defrost” by removing jumper JU1F on the main circuit board inside the electrical compartment
(see Section 9.0).
11- Plug in the unit and do the “overall verification” of the system as described in Section 11.0.
Y
R
GB
VD0026
F F I OC OL Y R G B
Y R G B
VE0072
VC0061
8.2 I
NSTALLATION OF THE
M
AIN
C
ONTROL
(cont’d)
figure 17
figure 18
figure 19