Jenn-Air W10274318A Manuale Utente

Pagina di 28
5
Back View
Cabinet Dimensions
IMPORTANT:
Minimum distance “X”: 30" (76.2 cm)
Suggested maximum distance “X”: 36" (91.4 cm)
Venting Requirements 
Vent system must terminate to the outdoors.
Do not terminate the vent system in an attic or other enclosed 
area.
Do not use a 4" (10.2 cm) laundry-type wall cap.
Use metal vent only. Rigid metal vent is recommended. 
The length of vent system and number of elbows should be 
kept to a minimum to provide efficient performance.
For the most efficient and quiet operation:
Use no more than three 90° elbows.
Make sure there is a minimum of 24" (61.0 cm) of straight 
vent between the elbows if more than 1 elbow is used.
Do not install 2 elbows together.
Use clamps to seal all joints in the vent system.
The vent system must have a damper. If roof or wall cap has a 
damper, do not use damper supplied with the range hood.
Use caulking to seal exterior wall or roof opening around the 
cap.
The size of the vent should be uniform.
Cold Weather Installations
An additional back draft damper should be installed to minimize 
backward cold air flow and a thermal break should be installed to 
minimize conduction of outside temperatures as part of the vent 
system. The damper should be on the cold air side of the thermal 
break.
The break should be as close as possible to where the vent 
system enters the heated portion of the house.
Makeup Air
Local building codes may require the use of makeup air systems 
when using ventilation systems greater than specified CFM of air 
movement. The specified CFM varies from locale to locale. 
Consult your HVAC professional for specific requirements in your 
area.
Venting Methods
This canopy hood is factory set for venting through the roof or 
wall.
A 3
¹⁄₄" x 10" (8.3 x 25.4 cm) rectangular vent system is needed for 
installation (not included). The hood exhaust opening is 3
¹⁄₄" x 
10" (8.3 x 25.4 cm). Vent system can terminate either through the 
roof or wall. To vent out of the top of the range hood and through 
a wall, a 90° elbow is needed. See “Install Range Hood” section 
for details for installing the damper.
NOTE: Flexible vent is not recommended. Flexible vent creates 
back pressure and air turbulence that gently reduce performance.
A. 76" (193.0 cm) minimum for 
installations with canopy only.
B. 88" (223.5 cm) minimum for 
installations with optional 
duct cover.
1
⁹⁄₃₂
"
(3.2 cm)
8
¹⁄₈
" (20.6 cm): 30" (76.2 cm) models
11" (27.9 cm): 36" (91.4 cm) models 
Wiring knockout
7
⁷⁄₈
"
(20.0 cm)
12
³⁄₁₆
" (31.0 cm): 30" (76.2 cm) models 
12
¹⁄₈
" (30.8 cm): 36" (91.4 cm) models 
¾" 
(1.9 cm)
13" (33.0 cm)
 
18" (45.7 cm) min.
 
 
clearance upper
cabinet to countertop
36" (91.4 cm)
countertop height
30" (76.2 cm) or 36" (91.4 cm) 
cabinet opening width
(If installed between cabinets)
A B
 
 X
 
Bottom of canopy
to cooking surface
Min. cabinet 
opening width
Duct cover (if used)
Canopy