Beckett SLD5125 Manuale Utente

Pagina di 32
 
25
Burner Goes Off On Safety 
Oil  Tank Full
Bleed Oil Lines
Oil Flows Freely
Air in Oil Lines
Pump Pressure
to Burner Spec.
Spark
Established
Nozzle Clean
Matches Burner
Setting
Air Setting Match
Preliminary
Settings
Fill Tank
Fuel Supply
Valves Open
Open All Supply
Valves
Oil Filter Clean
Pump Strainer
Clean
Replace Oil Filter
Clean or Replace
Strainer
Check All Fitting
Connections
Adjust Pressure
to Burner Specs.
Ignition Electrode
Shorted or Cracked
Refer to Burner
Manual
Replace Electrodes
Refer to Burner
Manual
Replace Nozzle
Adjust to
Preliminary Settings
Refer to Burner Manual
for Control
Troubleshooting
No
Yes
No
Yes
Yes
No
No
Yes
No
Yes
No
No
No
No
No
Yes
Yes
Yes
No
No
Yes
Yes
Yes