Configuration, Startup, and Operation 
 
 
of Recorder with Display 
12/03 
DR4300 Circular Chart Recorder Product Manual 
99 
Lower Display 
Prompt 
Upper Display  
Range of Setting  
or Selection 
Parameter  
Definition 
MINRPM 
RPM 
MIN   [factory setting] 
MINUTES PER REPEAT or REPEATS PER MINUTE
Use this parameter to choose whether you want to specify 
the integral term (reset) in the PIDA algorithm in terms of 
length (minutes per repeat) or frequency (repeats per 
minute). Your choice here affects which tuning prompt, “I 
MIN” or “I RPM”, is displayed. 
The relationship between the two ways of thinking about 
reset is demonstrated by this example: 
20 repeats per minute = 0.05 minutes per repeat. 
This parameter is displayed only if the “CTRALG” (control 
algorithm) is set to “PIDA”. 
ATTENTION
 If the setting of MINRPM is changed, 
you must change the value of the associated tuning 
parameter (“I MIN” or “I RPM”) if you want to maintain the 
same control action. For example, suppose MINRPM = I 
RPM and the value of tuning parameter “I RPM” = 2. If 
you change MINRPM to I MIN, the value of “I MIN” will 
now be 2 (the value formerly assigned to “I RPM”). If you 
want the same control action you had before, you must 
change the value of “I MIN” to 0.5.