Input and Output Calibration for Recorder with Display
12/03
DR4300 Circular Chart Recorder Product Manual
147
5.4.2 Thermocouple Inputs Using a Compensated Calibrator
Table 5-5 Set Up Wiring Procedure for Thermocouple Inputs
Using a Compensated Calibrator
Step Action
1
Connect the thermocouple extension wire to the calibration source (see Figure 5-2).
2
Connect the other end of the thermocouple extension wires to the TB2 terminals on the printed
circuit assembly for the input channel being calibrated.