8.6  Alignment of Pen at Zero and Span 
Introduction 
If the pen trace does not track at the correct chart increment with a known input value, you can use the 
following procedure to adjust the pen travel at zero and span (full scale) to compensate for the effects of 
humidity on the chart size.    
If the recorder has 2 pens, be sure Input1 (INP 1) is on the display. If it is not on display, press  FUNC   
key to toggle input for display. 
 
Procedure 
Follow the procedure in Table 8-15 to align the pens. 
 
Table 8-15  Procedure for Aligning Pen at Zero and Span 
Step Press 
Action/Result 
SET 
UP
 
until you can see: 
ALIN
Upper Display
 
PEN
Lower Display
 
FUNC
 
 
 
 
until you can see: 
(value)
Upper Display
(approximately 60 on the upper display) 
PEN0
Lower Display
 
Wait until pen stops moving downscale.  
If the pen tip is greatly out of position, follow Steps 3 through 7. (Unless a pen arm has been 
replaced, this probably will not be necessary.) If pen position requires only minor adjustment, go to 
Step 8.
 
 
Turn off the power to the recorder. 
 
To place the pen tips in approximately the correct position, loosen the screw 
holding the pen 1 (purple) arm to the servo shaft and move the pen arm to 
access the locking screw for the pen 2 (red) arm (if applicable). 
 
Align the tip of pen 2 with the zero line on the chart and tighten the locking 
screw. 
 
Align the tip of pen 1 with the zero line on the chart and tighten the locking 
screw. 
 
Turn on the power and repeat Step 2.