Pressure Systems 9046 Manuale Utente

Pagina di 72
Pressure Systems, Inc.                                                                                        Model 9046 User’s Manual 
 
 
 
Page 53 
 
www.PressureSystems.com 
5.7.4  Command ’c’- Sub-command Index 03: Clear Stream(s
This sub-command is used to "undefine" any previously configured host stream in a module, 
one at a time, or all together. The sub-command’s format is:
 
 
Command 
 
c 03 st” 
 
‘c’  is the operation code 
‘03’ is the sub-command index (‘ii’) for 
configuration 
st’ is the stream identifier character (1, 2, or 3 or 
0=all streams 
NOTE: all parameters are separated by a space
 
character
.
 
 
Response 
 
A” or “Nxx” 
‘A’ for acknowledge; ‘N’ for negative acknowledge, 
error code xx
.
 
 
Autonomous 
Packet 
 
none generated
 
 
Description
: This sub-command clears (un-defines) the particular specified host stream (st=1-
3), or un-defines “all configured” host streams with a single command (st=0). Once cleared, a 
stream must be reconfigured before it can be started. 
Example
Stop all the streams configured previously.  Then clear (un-define) only stream 3.  Finally, 
resume the remaining defined streams 1 and 2: 
"c 02 0
"c 03 3
"c 01 0
Read response: 
"A
"A
"A