D. Battery Test Function 
 
The UPS shall be provided with a “Battery Test” pushbutton to periodically 
check the condition of the batteries.  Upon detection of a battery problem, 
the UPS shall notify the user of this condition allowing the user to perform 
a detailed check of the battery string. 
 
 
7.0 SERVICE AND WARRANTY 
 
A. Reliability 
 
System mission reliability 240,000** hours and including bypass MTBF  
(Mean-Time-Between-Failure) shall be in excess of 3,000,000**hours.  
 
B. Maintainability 
 
Calculated and demonstrated MTTR (Mean-Time-To-Repair) shall be 30 
minutes including time to diagnose the problem and replace subassembly. 
 
C. Warranty 
 
The UPS system shall be provided with a comprehensive three-year on-
site warranty (when purchased with a Factory-Authorized Start-up).  
The warranty shall cover parts, labor, travel and freight for the UPS.  The 
battery system has a full 2 year warranty with 8 years prorata total of 10 
years warranty. Typical on-site response time shall be 4 hours (24 hours 
maximum).  The warranty period shall expire three years for UPS and two 
years for the battery system from date of shipment from manufacturer’s 
facility.   
 
 
 
*Specification subject to change without notices. 
**Times are accurate provided normal Preventative Maintenance procedures are 
followed.