7.5  Power Range 1000 VA (19” Rack-mount model, HV, 1U & 2U)
General
Rated power:
1000 VA at power factor 0.7
Technology:
On-line, double conversion topology with automatic
bypass
Input
Phase:
Single phase with ground
Bypass Voltage: 
184VAC- 265VAC
Input Voltage range: 
160VAC-276VAC
Frequency:
50/60 Hz Auto selection
Frequency window from main supply:
45-65 Hz
Synchronization window:
± 3Hz
Input current:
1000 VA 4A
Input Power factor:
0.97
Output
Output Voltage:
208/220/230/240 VAC, selectable from LCD panel
Voltage regulation:
± 2%
Voltage distortion:
< 5% THD at full non-linear load, < 3% THD at full
linear load
Frequency regulation:
± 0.25 Hz (battery or free running mode)
Dynamic response:
± 9 % max from 100% to 20 % or from 20% to 100 %
linear load
Overload capacity:
100-125% 1 min, 125-150% 10 sec
Efficiency:
greater than 86%
Environmental
Ambient temperature:
+0 °C to +40 °C
Recommended temperature:+15 °C to +25 °C
Storage temperature:
-15 °C to +50 °C
Cooling:
Forced air-cooling
Humidity:
0-95%, non-condensing
Audible noise:
< 45 db normal and battery mode (1000 VA)
< 50 db normal and battery mode (1200 VA)
Standard
Safety: EN50091-1-1
Emissions: EN50091-2
Immunity: 
EN50091-2 B (1000-1200VA)